Application:

Uninterruptible Power Supply(UPS); Emergency Power Supply(EPS);

Emergency Backup Power;               Emergency Light;

Railway System;                                Aircraft Signal System;

Alarm and Security Systems;            Electronic Instruments and Equipment;

Telecom Communication System;     DC Screen Power Supply;

Navigation Mark Signal System;        Solar Wind Energy System.


XD200-12 Battery (12V200Ah)

  • XD200-12 Battery (12V200Ah)
XD200-12 Battery (12V200Ah)
  • 产品介绍
  • 右边简介
  • 产品介绍(手机)

specification
Nominal Voltage12V
Nominal Capacity   (10HR)150AH
Battery   sizeLength485±3mm (19.09 inches)
Width170±2mm (6.69 inches)
Height240±2mm (9.45 inches)
Total Height (including terminal)240±2mm (9.45 inches)
Weight41.1 kg (90.61 lbs)
Terminal   typeT11
Housing   materialABS
Rated Capacity156.0 AH/7.80A (20hr   ,1.80V/Cell,25℃/77℉)
150.0   AH/15.0A (10hr,1.80V/Cell,25℃/77℉)
129.0   AH/25.8A (5hr,1.75V/Cell,25℃/77℉)
117.0   AH/39.0A (3hr,1.75V/Cell,25℃/77℉)
91.5   AH/91.5A (1hr,1.60V/Cell,25℃/77℉)
Maximum Discharge   Current1500A (5s)
Battery Internal   Resistance3.5 mΩ
Operating
    Temperature Range
Discharging-15 ~ 50℃ (5 ~ 122℉)
Charging0 ~ 40℃ (32 ~ 104℉)
Storage-15 ~ 40℃ (5~ 104℉)
Rated   Operating Temperature25±3℃ (77±5℉ )
RecycleAt a   temperature of 25 °C and  a   voltage  of  14.4 V to 15.0 V,  the initial charge current is
     less than 45.0 A.  The correction  factor    is -30mV/°C
Floating   Charge At a   temperature of 25℃ and a voltage of 13.5 V to 13.8 V, the initial charging   current
     is not limited. The correction   factor is -20mV/°C
Capacity affected
      by temperature
40℃(104   ℉)103%
25℃( 77 ℉ )100%
0℃( 32 ℉ )86%
Self-dischargeAt a   temperature of 25℃, the battery can store up to 6 months and then need to be   recharged once.  If the battery is   stored
    at a higher temperature, the storage interval will be shortened

Constant current   discharge meter at 25 °C (77 °F)( Amperes)

Voltage
               Time
5 minutes10 minutes15 minutes20 minutes30 minutes45 minutes1 hour2 hours3 hours4 hours5 hours6 hours8 hours10 hours20 hours
1.85V/Cell256.7201.8171.6143.6114.186.470.745.035.629.123.520.416.614.27.73
1.80V/Cell344.6257.9207.4169.7134.6100.479.249.238.331.125.221.917.615.07.8
1.75V/Cell388.5283.4226.5182.6139.8104.282.951.039.031.825.822.517.915.17.88
1.70V/Cell427.9308.9241.8191.9145.5108.485.553.040.132.626.52318.115.38.03
1.65V/Cell471.8333.3257.2203.8153.5111.188.454.541.833.727.223.518.415.68.13
1.60V/Cell520.4361.9275.0217.1162.0115.891.556.343.134.828.124.018.615.88.18